FA-I-V, FA-I-P
Flame Arrester for vacuum pumps, compressors and blowers

Features
Versatilidade de aplicações
Possibilidade de diversas aplicações
Design modular
Permite a substituição e a limpeza de FLAMEFILTER® individual
Peças de reposição
Peças de reposição com excelente custo-benefício
Function and Description

Against the Propagation of Explosions
PROTEGO® FA-I-V and FA-I-P Flame Arresters are specifically designed for
vacuum
Dépression
Vacuum is the pressure in an enclosed space that is lower than the ambient pressure.
pumps, blowers, and compressors. The high flow velocity in the small gaps of these machines can lead to undesirable ignitions within the
housing
Corps
A housing is a solid shell, which surrounds a content, either protecting the content from external influences, or protecting the environment from the content.
. One of the safest measures against explosion propagation are Flame Arrester Unit that are installed on the vacuum and pressure side of the equipment.
Unique Modular System for Optimized Flame Arresters
PROTEGO® FA-I-V devices for the vacuum side and PROTEGO® FA-I-P devices for the pressure side provide a unique modular design that gives every manufacturer of vacuum pumps or comparable devices the option of using optimized and adapted Flame Arresters. Our expert technical staff will assist you with the proper selection of the devices as well as execution of type testing.

Main Component – PROTEGO® Flame Arrester Unit
PROTEGO® FA-I-V and FA-I-P devices are symmetrical in design. The arrester essentially consists of two housing parts (1) and the PROTEGO® Flame Arrester Unit (2) in the center. The PROTEGO® Flame Arrester Unit is modular and consists of several FLAMEFILTER® (3) and spacers firmly held in a
FLAMEFILTER® cage
Cage d'éléments arrête-flammes
The FLAMEFILTER® cage is a housing for a FLAMEFILTER® set.
. The number of FLAMEFILTER® and their gap size depends on the arrester´s conditions of use. PROTEGO® FA-I-V and FA-I-P Flame Arresters are available for explosion groups IIA to IIC (NEC groups D to B) and special gases such as Ethylene oxide.
Product Data
Tabela de dimensões
Dimensões em mm
Seleção do grupo de explosão
| FLAMEFILTER® gap | MESG | Expl. Gr. (IEC / CEN) | Gas Group (NEC) |
| 0.7 mm | > 0.90 mm | IIA | D |
| 0.5 mm | ≥ 0.65 mm | IIB3 | C |
| 0.3 mm | ≥ 0.50 mm | IIB | C |
| 0.2 mm | < 0.50 mm | IIC | B |
Seleção do material do corpo
| Design | A | B | C |
| Housing | Steel | Stainless steel | Hastelloy |
| Gasket | PTFE | PTFE | PTFE |
| Flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. | A, B | B | C |
The housing can also be delivered in steel with an ECTFE coating Revêtement Coating is the application of a firmly adhering layer of shapeless material to the surface of a workpiece. .
Special materials upon request
Combinações de material do conjunto abafador de chamas
| Design | A | C | D |
| FLAMEFILTER® cage | Steel | Stainless Steel | Hastelloy |
| FLAMEFILTER®* | Stainless Steel | Stainless Steel | Hastelloy |
| Spacers | Stainless Steel | Stainless Steel | Hastelloy |
* the FLAMEFILTER® is also available in the materials Tantalum, Inconel, Copper, etc. when the listed housing and cage materials are used.
Special materials upon request
Tipo de conexão flangeada
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |

Finding your location…
PROTEGO®
Representative