UB/SF-IIA1
Pressure/Vacuum Diaphragm Valve with internal coating, deflagration- and endurance burning-proof

Features
Extreme Tightness
Optimal Pressure Maintenance
Protective System According to ATEX
Digital Level Monitoring
Digital Level Sensors
Frost-Proof
Condensate Drainage
Monitoring
Modular Design
Easy Operation Monitoring
Safety Against Endurance Burning
Safe Venting

Combined Pressure and Vacuum Relief Valve

Usable Under Extreme Climatic Conditions

Composition
Advanced Sealing Technology for Reliable Pressure Maintenance in Tanks
Dynamic Flame Arresting Safety at Overpressure Conditions
Many Individual Certifications
Dimensions
To select the nominal size (DN), please use the flow capacity charts on the following pages
| DN | pressure | pressure | 80 / 3" | pressure | pressure | 100 / 4" | pressure | pressure | 150 / 6" |
| a | up to +28 mbar | up to +11.2 inch W.C. | 615 / 24.21 | up to +28 mbar | up to +11.2 inch W.C. | 645 / 25.39 | up to +25 mbar | up to +10 inch W.C. | 680 / 26.77 |
| a | > +28 mbar | > +11.2 inch W.C. | 765 / 30.12 | > +28 mbar | > +11.2 inch W.C. | 795 / 31.30 | > +25 mbar | > +10 inch W.C. | 830 / 32.68 |
| b | 410 / 16.14 | 485 / 19.09 | 590 / 23.23 |
Dimensions in mm / inches
Pressure settings > +50 mbar / +20 inch W.C. (DN 80), > +45 mbar / +18 inch W.C. (DN 100), > +46 mbar / +18.4 inch W.C. (DN150) with additional liquid reservoir - dimensions upon request
Dimensions for pressure/vacuum diaphragm valves with heating coil upon request
Selection of explosion group
| MESG | Expl. Gr. (IEC / CEN) |
| ≥ 1,14 mm | IIA1 |
Special approvals upon request
Material for housing
| Design | B |
| Housing | Steel |
| Coating of housing | 2 components polymere coating |
| Valve top | Stainless Steel |
| Heating coil (UB / SF-H-...-I) | Stainless Steel |
| Valve seats | Stainless Steel |
| Gasket | FPM |
| Diaphragm | FPM |
Special materials upon request
Flange connection type
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |
other types upon request
Flow Capacity Chart


UB/SF DN100


UB/SF DN150


The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.