DR-UN
In-Line Detonation Flame Arrester for stable detonations and deflagrations in right angle design with shock absorber, unidirectional

Features
Fastest Disassembly and Assembly
Modular Design
Spare Parts
Use of Patented Shock Wave Guide Tube Effect (SWGTE)
Low Costs
Easy Maintenance

Secure Potentially Explosive Plants Against Pipe Deflagrations and Stable Detonations

For Explosion Groups IIA to IIB3
Dimensions
To select the nominal size (DN), please use the flow capacity charts on the following pages
| DN | 25/ 1" | 32 / 1 ¼" | 40 / 1 ½" | 50 / 2" | 65 / 2 ½" | 80 / 3" | 100 / 4" | 150 / 6" | 200 / 8“ |
| a | 100 / 3.94 | 125 / 4.92 | 140 / 5.51 | 150 / 5.91 | 160 / 6.30 | 185 / 7.28 | 250 / 9.84 | 300 / 11.81 | 350 / 13.78 |
| b | 125 / 4.92 | 150 / 5.91 | 160 / 6.30 | 165 / 6.49 | 185 / 7.28 | 195 / 7.68 | 250 / 9.84 | 300 / 11.81 | 350 / 13.78 |
| c | 189 / 7.44 | 214 / 8.43 | 259 / 10.2 | 264 / 10.39 | 307 / 12.09 | 317 / 12.08 | 374 / 14.72 | 464 / 18.27 | 707 / 27.83 |
| c1 | 280 / 11.02 | 310 / 12.20 | 370 / 14.57 | 375 / 14.76 | 485 / 19.09 | 495 / 19.49 | 585 / 23.03 | 705 / 27.75 | 1170 / 46.06 |
| d | 149 / 5.87 | 149 / 5.87 | 210 / 8.27 | 210 / 8.27 | 275 / 10.83 | 275 / 10.83 | 325 / 12.80 | 460 / 18.11 | 620 / 24.41 |
| e | - | - | - | - | 326 / 12.83 | 336 / 13.23 | 403 / 15.87 | 475 / 18.70 | 707 / 27.83 |
| f | - | - | 168 / 6.61 | 168 / 6.61 | - | - | - | - | - |
| g | - | - | 138 / 5.43 | 143 / 5.63 | - | - | - | - | - |
| h | - | - | 50 / 1.97 | 50 / 1.97 | - | - | - | - | - |
| xy | 475 / 18.70 | 500 / 19.69 | 570 / 22.44 | 580 / 22.83 | 690 / 27.17 | 700 / 27.56 | 770 / 30.31 | 905 / 35.63 | 1305 / 51.38 |
Dimensions in mm / inches
* upon request
Selection of explosion group
| MESG | Expl. Gr. (IEC / CEN) | Gas Group (NEC) |
| > 0,90 mm | IIA | D |
| ≥ 0,65 mm | IIB3 | C |
Selection of max. operating pressure
| Expl. Gr. | DN | 25/ 1" | 32 / 1 ¼" | 40 / 1 ½" | 50 / 2" | 65 / 2½" | 80 / 3" | 100 / 4" | 150 / 6" | 200 / 8“ |
| IIA | Pmax | - | - | - | 2,0 / 29.0 | 2,0 / 29.0 | 2,0 / 29.0 | 2,0 / 29.0 | 1,2 / 17.4 | 1,6 / 23.2 |
| IIB3 | Pmax | 1,4 / 20.3 | 1,4 / 20.3 | 1,4 / 20.3 | 1,4 / 20.3 | 1, 2 / 17.4 | 1, 2 / 17.4 | 1,2 / 17.4 | 1,2 / 17.4 | 1,1 / 15.9 |
Pmax = maximum allowable operating pressure in bar / psi (absolute)
Specification of max. operating temperature
| ≤ 60°C / 140°F | Tmaximum allowable operating temperature in °C |
Material selection for housing
| Design | B | C |
| Housing | Steel | Stainless Steel |
| Cover with shock absorber | Steel | Stainless Steel |
| O-Ring | FPM | PTFE |
| Flame arrester unit | A | C, D |
Special materials upon request
Material combinations of flame arrester unit
| Design | A | C | D |
| FLAMEFILTER® cage | Steel | Stainless Steel | Stainless Steel |
| FLAMEFILTER®* | Stainless Steel | Stainless Steel | Hastelloy |
| Spacer | Stainless Steel | Stainless Steel | Hastelloy |
* Other FLAMEFILTER® materials upon request
Special materials upon request
Flange connection type
| EN 1092-1; Form B1 |
| ASME B16.5 CL 150 R.F. |
other connections upon request
Flow Capacity Chart


The flow capacity charts have been determined with a calibrated and TÜV certified flow capacity test rig. Volume flow V in (m³/h) and CFH refer to the standard reference conditions of air ISO 6358 (20°C, 1bar). For conversion to other densities and temperatures refer to Sec. 1: “Technical Fundamentals”.