BE/HR-D

Pressure Relief Valve deflagration- and endurance burning-proof

Features

Plato de válvula guiado
El plato de válvula va guiado dentro del cuerpo para protegerlo frente a condiciones meteorológicas adversas
Sistema de protección conforme a ATEX
Puede utilizarse como sistema de protección en zonas con atmósferas potencialmente explosivas según ATEX
Extrema estanqueidad
Lo que se traduce en las menores pérdidas posibles de producto y en una reducción de la contaminación ambiental
Seguridad contracombustión prolongada
Protección contra deflagraciones atmosféricas y combustión prolongada
Apagallamas integrado
La unidad apagallamas PROTEGO® integrada ahorra espacio y peso y reduce costes
Flujo volumétrico
Flujo de caudal optimizado
Function and Description

Pressure Relief Valve with Integrated PROTEGO® Flame Arrester

The Deflagration-Proof and Endurance-Burning-Proof BE/HR-D Type PROTEGO® valve is a highly developed pressure relief valve Soupape de surpression Valve designed to open and relieve excess pressure and to reclose and prevent the further flow of fluid after normal conditions have been restored. with an integrated Flame Arrester Unit. It is primarily used as a device Appareil A device is a pipe component that influences the media flow by opening, closing, or partially shutting off the flow channel or by dividing or mixing the media flow. for flame transmission proof outbreathing on tanks, containers and process engineering apparatus. The valve offers reliable protection against excess pressure and prevents product losses almost up to the set pressure Pression de réponse Set pressure is the gauge pressure at the device inlet at which the relief device is set to start opening under service conditions. ; it also protects against atmospheric deflagration as well as endurance burning Endurance burning Stabilized burning for an unlimited time. if stabilized burning occurs. The PROTEGO® Flame Arrester Unit is designed to achieve minimum pressure drop with maximum safety. The BE/HR-D valve is available for substances of explosion group IIA (NEC group D MESG > 0.9 mm).

Advanced Manufacturing Technology

When the set pressure is reached, the valve starts to open and reaches full lift Course Lift is the actual travel of the valve pallet from the main valve out of the closed position. within 40% overpressure Surpression Overpressure refers to an increase in pressure in a system or vessel above the normal operating pressure. . The tank pressure Pression de la cuve Tank pressure is the pressure within a tank. is maintained up to the set pressure with a tightness that is far superior to the conventional standard due to our state of the art manufacturing technology. This feature is ensured by the valve seats made of high quality stainless steel and with individually lapped valve pallets (1) or with an air cushion seal Joint A seal prevents or limits unwanted transfer of product from one container to another. Seal is used as superordinate term for all types of sealing elements. (2) in conjunction with high quality FEP diaphragm Membrane A diaphragm is a thin layer of material, which has a large surface area. . After the excess pressure is discharged, the valve reseats and provides a tight seal.

Many Individual Certifications

If the set pressure is exceeded, explosive gas/product-vapour air mixtures are released to the atmosphere. If this mixture ignites, the integrated PROTEGO® Flame Arrester Unit (3) prevents flame transmission into the tank. If additional mixture continues to flow and stabilized burning occurs, the integrated Flame Arrester Unit prevents flashback as a result from endurance burning. The valve is protected and also fulfils its function under this severe service conditions. The spring Ressort A spring is a spiral of wire which returns to its original shape after it is pressed or pulled. loaded weather hood Capot de protection contre les intempéries A weather hood is a cover to protect the internal components of a device from environmental influences. opens as soon as the fusible element (4) melts. The valve can be used up to an operating temperature Operating temperature Temperature reached when the equipment is operating under design conditions. of +60°C / 140°F and meets the requirements of European Tank Design Standard EN 14015 – Appendix L and ISO 28300 (API 2000). EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.
Product Data

Dimensiones

To select the nominal size Diamètre nominal The nominal size is an alphanumeric designation of size for components in a piping system, used for reference purposes, comprising the letters DN followed by a dimensionless integer that is indirectly related to the physical size of the bore or outside diameter of the connections, expessed in millimeters. (DN), please use the flow capacity chart on the following page

DN150 / 6" 200 / 8"
NG400 / 16"400 / 16"
a600 / 23.62600 / 23.62
b545 / 21.46545 / 21.46
c485 / 19.09485 / 19.09NG = Nominal size

Dimensiones en mm / pulgadas

Selección del grupo de explosión

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
> 0,90 mmIIAD

Special approvals upon request

Selección de materiales para la vivienda

DesignAB
HousingSteelStainless Steel
Valve seatStainless SteelStainless Steel
Weather HoodSteelStainless Steel
Flame arrester unit Flame arrester unit Flame arrester casing with FLAMEFILTER® set. AB

Special materials upon request

Combinación de materiales para la unidad apagallamas

Design  AB
FLAMEFILTER® cageSteelStainless Steel
FLAMEFILTER®Stainless SteelStainless Steel

Special materials upon request

Material selection for valve pallet

Design ABC
Pressure range [mbar]
[inch W.C.]
+2.0 up to +3.5
+0.8 up to +1.4
>+3.5 up to +14
>+1.4 up to +5.6
>+14 up to +35
>+5.6 up to +14
Valve palletAluminiumStainless SteelStainless Steel
SealingFEPFEPMetal to Metal

Special materials and higher pressure settings upon request

Tipo de bridas de conexión

EN 1092-1; Form B1
ASME B16.5 CL 150 R.F.

other types upon request

Diagrama de flujo volumétrico

Los diagramas de flujo volumétrico han sido determinados con un banco de pruebas de caudal calibrado y certifi - cado por TÜV. El flujo volumétrico V. en [m³/h] y el CFH se refi eren a las condiciones estándar de referencia de aire según ISO 6358 (20°C, 1bar). La conversión a otras densidades y temperaturas están referidas en el Vol. 1: “Fundamentos Técnicos”.

Detail X

Detail X

Applications

Tanques de almacenamiento

Instalaciones de procesamiento químico y farmacéutico

Energías renovables

Tratamiento con vapor